Installation & safety

Install safely.
Keep accessible.

System installation combines mechanical hold, matched securing and a controlled service route. The specific profile combination is decisive.

Technical drawing · connector and fall protection for surface mounting.
Technical drawing · connector and fall protection for surface mounting.
Three systems. Clear assignment.

The securing follows the installation type.

Installation situationUpper fixingFastening to the luminaire profile
ConcreteConcrete retaining clip only in the mounting profile; never in the flush-mount driver profile.Connector pair in both rear longitudinal slots of the suitable visible profile.
Flush-mount / flange profilesFlush-mount retaining clip only in the mounting profile; never in the flush-mount driver profile.Connector pair in both rear longitudinal slots of the suitable visible profile.
Surface-mounted / APFree eyelet on the load-bearing substrate. With a suitable version, fastened to the mounting base by LL2509.The connector pair stays in the longitudinal slots of the secured visible profile.

LL2509:
The important distinction.

LL2509 has no longitudinal slots on the rear for the connector pairs of the three securing sets. It can therefore not be secured on its own as a mini profile, blind cover or transformer cover.

If a suitable visible profile is mounted on LL2509, LL2509 may serve as the mounting base: the connector pair stays in the visible profile; the ring eyelet of the AP securing is screwed through LL2509 at the intended fixing point.

LL2509 and its functions
Surface-mount installation – fixing and fall protection
Clips and construction sequence

Installation means more than clipping in.

TopicExecution note
Mounting clipsFour per metre, rounded up and at least two per section. V1 / V2 / V3 with 10 / 20 / 30 mm to match the actual installation depth.
Driver profile UPMaximum driver height 18 mm. Remove the tear-off tab only after the profile has been fully installed. Check device dimensions, connections and removal path.
Mechanics and electricsA fall-protection device does not replace a required protective earth connection. Connection, protection concept and testing by a qualified electrician.
Magnetic mountingMounting base plate and magnet are a separate fixing system. Check load capacity, mating surface and M4 securing in accordance with the installation chapter.
Building surfaceInstall the luminaire insert only after plastering, filling and painting work is complete. Clean the profile channel and measure the installation height.
AccessHold the safety device in a controlled manner, safely isolate the electrical installation, remove the insert and use the appropriate service path.
PDF

Complete safety and installation notes

PDF · Original document

PDF

Binding installation correction V2/V3

14.11.2026 · Restore original tips after shortening

Open original view ↗